Section 3
Auto-Zone Basic
3-4 Programming
Status Screen #3
Status Screen #4
Line 2 - Current Zone Damper Position
Line 3 - Currently active Minimum Damper/Airflow
Setpoint. Each mode has its own minimum setpoint.
These modes are vent, cooling and heating.
Line 4 - Currently active Maximum Damper/Airflow
Setpoint. This value is user adjustable and is used in
all modes of operation, unlike the Minimum
Damper/Airflow Setpoint.
Zone Number 1
Damper Pos 20
Minimum Setpt 20
Maximum Setpt 100
Line 2 -
Auxiliary Heat Off
Box Heating On
Aux Heating On
Box & Aux Heat On
Line 3 -
Series Fan On
or
Blank Line if Fan is Off
Line 4 -
Parallel Fan On
or
Blank Line if Fan is Off
Zone Number 1
Auxiliary Heat Off
Series Fan On