Basic system communications checklist – Auto-Zone Control Systems Auto-Zone Basic Systems Installation & Operation (Version 02C) User Manual
Page 109

Auto-Zone Basic
Section
4
Start-Up & Troubleshooting
4-7
Basic System
Communications Checklist
Basic System without Optional CommLink
Zone Manager is correctly addressed as 0
Zone Controllers are correctly addressed from 1 to 16
Power has been cycled after changing addresses
There are no duplicate addresses on the loop
The first Zone Controller on the communication loop is connected to the
Zone Manager communication terminal
All communication wiring is landed correctly, T to T, R to R, and SHLD to SHLD
All Zone Controllers are wired to 24 Volt AC power supply
Zone Manager is wired to 24 Volt AC power supply
All 24 VAC power wiring is landed correctly - 24VAC to 24VAC and GND to GND
Zone Manager is powered up
Zone Controllers are powered up
Additional Checks for Basic System with
Optional CommLink IV
CommLink IV is connected to the communications loop
CommLink IV is set for single loop operation
Zone Manager is correctly addressed as 17
CommLink IV is wired to 24 Volt AC power supply
CommLink IV is powered up
Other Optional Equipment
Computer is correctly connected to the CommLink IV
Prism™ software is installed on a computer
Remote Link II is correctly connected to the CommLink IV
Remote Link II is connected to a working phone line
Second Remote Link II is connected to a computer and working phone line off-site
IP Module is correctly installed in the CommLink IV
CommLink IV with installed IP Module is connected to an Ethernet router for off-site
communications