Auto-zone basic, Installation and wiring – Auto-Zone Control Systems Auto-Zone Basic Systems Installation & Operation (Version 02C) User Manual
Page 52

Section 2
Auto-Zone Basic
2-22
Installation and Wiring
Figure 2-16: Room Sensor Wiring
Connect the terminal labeled GND on the zone sensor to the terminal labeled GND on the
Zone Controller terminal block for the TEMP SENSOR. Connect the terminal labeled
TMP on the zone sensor to the terminal labeled TEMP on the Zone Controller terminal
block for the TEMP SENSOR. If the zone sensor has a setpoint adjust slider, connect the
sensor terminal labeled AUX to the Zone Controller AUX terminal block labeled AUX1.
GND
AUX
TMP
OVR
R
E
L
O
C
R
E
M
R
O
A
W
Room Sensor
Zone Controller
AUX
TEMP
GND
GND
AUX1
+VS
AUX2
TB2
++
TB1TB1
Connection To AUX
Terminal Required Onl
y
When Sensor Is Specified
With Slide Adjust Option