beautypg.com

3 shutdown application – contact closure, Shutdown application – contact closure -18 – AMETEK DLM Series User Manual

Page 62

background image

Advanced Operation

DLM-E 3kW & 4kW Series Power Supplies

Figure 4–12. Using Shutdown with a DC Input (Positive Logic)

4.5.3

Shutdown Application – Contact Closure

An external relay, whether normally open or normally closed, may be used to activate the
Shutdown circuit. Either positive or negative logic may be used.

To activate the Shutdown function using an external relay:

1. Turn off the power supply.

2. Connect one side of the external relay to pin 15 (+5 VDC Auxiliary Output) on connector

J3. Connect the other side of the relay to J3-pin 14 (Remote Shutdown Input). Also
connect pin 2 (Shutdown Return) to pin 6 (Status Indicator Return). See Figure 4–13
through Figure 4–16.

3. Set rear panel DIP switch S1 to select the desired circuit logic as defined in the following

table.

Relay

Switch S1-6 Setting

Relay Coil State Output

Normally Open Relay

UP–Open (Positive Logic)

Energized OFF

De-energized ON

DOWN–Closed (Negative Logic)

Energized ON

De-energized OFF

Normally Closed Relay

UP–Open (Positive Logic)

Energized ON

De-energized OFF

DOWN–Closed (Negative Logic)

Energized OFF

De-energized ON

The red S/D (Shutdown) LED on the front panel lights up when the Shutdown circuit is
activated.

4-18

M362000-01 Rev E