Advanced Operation

DLM-E 3kW & 4kW Series Power Supplies

4.3.3

Programming Output Current Limit

Programming Output Current Limit with a 0–5 VDC or 0–10 VDC Source

1. Set S1-2, the rear panel DIP Switch, UP, in the open position for 0–5 VDC programming

range.

2. Set S1-2, the rear panel DIP Switch, Down, in the closed position for 0–10 VDC

programming range.

3. Connect the external programming source between pins 10 (current programming

input/positive) and 12 (return). Varying the programming voltage from 0 to maximum will
cause the output to vary from 0 to 100% of the model rating. Adjust the programming
signal to zero.

4. Turn the power supply ON.

5. Set the front panel LOCAL/REMOTE switch to the REMOTE position and adjust the

external programming voltage source. By pressing the V&I PREVIEW button and
observing the front panel ammeter reading, the external control can be adjusted to the
desired setting.

S1 Switch Settings

S1-2 OPEN = 0–5V

S1-2 CLOSED = 0–10V

Figure 4–6. Programming Output Current Limit with a 0–5 VDC or 0–10 VDC Source