beautypg.com

2 programming output voltage, Programming output voltage -8 – AMETEK DLM Series User Manual

Page 52

background image

Advanced Operation

DLM-E 3kW & 4kW Series Power Supplies

4.3.2

Programming Output Voltage

Programming Output Voltage with a 0–5 VDC or 0–10 VDC Source

1. Set S1-1, the rear panel DIP Switch, UP, in the open position for 0–5 VDC programming

range.

2. Set S1-1, the rear panel DIP Switch, DOWN, in the closed position for 0–10 VDC

programming range.

3. Connect the external programming source between pins 9 (voltage programming

input/positive) and 12 (return). Varying the programming voltage from 0 to maximum will
cause the output to vary from 0 to 100% of the model rating. Adjust the programming
signal to zero.

4. Turn the power supply ON.

5. Set the front panel LOCAL/REMOTE switch to the REMOTE position and adjust the

external programming source voltage. By pressing the V&I PREVIEW button and
observing the front panel voltmeter reading, the external control can be adjusted to the
desired setting.

S1 Switch Settings

S1-1 OPEN = 0–5V

S1-1 CLOSED = 0–10V

Figure 4–4. Programming Output Voltage with a 0–5 VDC or 0–10 VDC Source

4-8

M362000-01 Rev E