Chapter 3: Operation

Table 3-6. Contacts Provided by the XUSR Connector

Pin
Pairs

Description

Comments

Voltage-Free Contacts Provided by Customer

1, 14

User E-Stop CH 1 (mushroom push-
button, safety gates, etc.)

N/C contacts, Shorted if NOT Used

2, 15

User E-Stop CH 2 (same as pins
1, 14)

N/C contacts, Shorted if NOT Used

3, 16

Line E-Stop (used for other robot or
assembly line E-Stop inter-
connection. Does not affect E-Stop
indication (pins 7, 20))

N/C contacts, Shorted if NOT Used

4, 17

Line E-Stop (same as pins 3, 16)

N/C contacts, Shorted if NOT Used

5, 18

Muted safety gate CH 1 (causes E-
Stop in Automatic mode only)

N/C contacts, Shorted if NOT Used

6, 19

Muted Safety Gate CH 2 (same as
pins 5, 18)

N/C contacts, Shorted if NOT Used

Voltage-Free Contacts provided by Adept

7, 20

E-Stop indication CH 1

Contacts are closed when Front Panel, pend-
ant, and customer E-Stops are not tripped

8, 21

E-Stop indication CH 2 (same as
pins 7, 20)

Contacts are closed when Front Panel, pend-
ant, and customer E-Stops are not tripped

9, 22

Manual/Automatic indication CH 1

Contacts are closed in Automatic mode

10, 23

Manual/Automatic indication CH 2

Contacts are closed in Automatic mode

11, 12,
13, 24,
25

No connection

Table 3-7. Contacts Provided by the XFP Connector

Pin
Pairs

Description

Requirements for User-
Supplied Front Panel

Voltage-Free Contacts Provided by Customer

1, 9

Front Panel E-Stop CH 1

User must supply N/C con-
tacts

2, 10

Front Panel E-Stop CH 2

User must supply N/C con-
tacts

3, 11

Remote Manual/Automatic switch CH 1.
Manual = Open Automatic = Closed

Optional - jumper closed for
Auto Mode-only operation