Figure 44: Screen used to create a new micro-grid�
Fill in the following fields to create a new micro-grid,
:
Table 6:New micro-grid: Micro-grid information�
Parameter
Description
Name
Name of the micro-grid
Micro-grid identifier
Select the ID no. of the micro-grid
(Drop-down list, from 1 to 100)
Operator
(1)
Name of the operator
Phone
Contact number of the operator
Geographical coordinates:
(1)
Latitude and Longitude
Latitude and longitude of the micro-grid
(1)
These fields are not mandatory.
If you want the micro-grid to operate in the
Frequency mode, enter the frequency values for
each state of the micro-grid,
.
Table 7: New micro-grid: Frequency mode�
Parameter
Description
Default value
(2)
Type of micro-grid
Select the type of generators used in the mi-
cro-grid:
Solar power with batteries, Diesel
generator or Other.
Solar power with batteries
Frequency
Working frequency of the micro-grid
50 Hz
Hysteresis between
mode changes
Time between the change of states, in seconds
300 s.
Excess
Input frequency of the excess factor
52.5 Hz
Limitation
Input frequency of the limiting factor.
48.5 Hz
Bonus
Input frequency of the bonus factor
52 Hz
Restriction
Input frequency of the restriction factor
49 Hz
Auxiliary relay activa-
tion
Frequency required to activate the auxiliary relay.
52 Hz
(2)
Default values for a solar power micro-grid with 50Hz batteries.