Technical specifications – CIRCUTOR computer PLUS-TF Series User Manual
Page 9

9
2
TECHNICAL SPECIFICATIONS
Auxiliary power supply:
110 to 480 Vac (50…60 Hz) (± 10%)
Consumption of the unit:
6.6 VA / 230 V ÷ 19 VA / 400 V ÷ 24.9 VA / 480 V
Voltage circuit:
Measurement margin
5% to 120 % for Un = 300 Vac (phase-neutral)
5% to 120 % for Un = 520 Vac (phase-phase)
Maximum consumption
< 0.6 VA
Frequency
45 ... 65 Hz
Intensity circuit:
Nominal current
Transformers In / 5 Aac or In / 1 Aac
Admissible overload
6 A permanent, 100 A t< 1 s
Consumption (…/5 A and …/ 1
A)
< 0.45 VA
Integrated control system
FCP or Linear / 4 quadrants
Integrated control algorithms
Three-phase and Phase-Phase (Star or Delta)
Communications of Computer
plus with CPC3i (Non-
configurable):
Bauds
38400 bps
Parity
NO
No. Bits \ Stop
8 / 1
Frame
See Section 13
Environment:
Operating temperature
-10º to +50 ºC
Storage temperature
-20º to +65 ºC
Maximum relative humidity
95 % non-condensing
Maximum operating altitude
2000 m (over sea level)
Installation category
Installation category III, in accordance with IEC 61010
Contamination level
2, in accordance with IEC 61010
Protection degree
IP 51 front panel - IP 20 rear panel
Safety:
Installation category
Installation category III, in accordance with IEC 61010
Protection to electric shock
Double insulation class II
Designed and identified with the CE mark