Etting, Plug&play step 1 – CIRCUTOR computer PLUS-TF Series User Manual
Page 30

30
Fig.20.- Password request
7.2
"Plug & Play" Setting
One of the most important features of Computer plus when compared to other cheaper regulators is its
configuration advantages. Computer plus is a very sophisticated regulator and it has a Plug & Play option
in the setup menu. The following data must be entered in this option:
Power of each capacitor step
Voltage and connection of capacitors (star or delta).
ATTENTION: The Plug & Play setting is always in the three-phase mode, even when you have
selected the phase-phase control option.
1) During the Plug&Play setup, the device will connect a capacitor step to measure the ratio of the
current transformers (CT)
2) The kvar data of each capacitor step at nominal voltage is labelled on each capacitor.
With this information, the device can configure all other parameters by simply pressing a key, thus saving
time and preventing any errors. After calculating the installation's setup and before starting the automatic
regulation mode, the device will display a report of the setup of the different parameters and request for
confirmation.
The steps that must be followed to configure the device in the Plug & Play mode are as follows:
7.2.1
Plug&Play Step 1
Go to the main menu (Fig. 21)
Use the arrows to
select the folder
and press
OK
. Fig.22 will be displayed on
the screen.