Standard function blocks – Pilz ST SB DP S, SW paket PROFIBUS-DP User Manual
Page 35

PROFIBUS-DP-Slave Operating Manual
6-3
Standard Function Blocks
ERR (hex) Key
Cause/Remedy
00FD
DP_SL_ERR_CHK_CFG
Configuration data on Master and Slave
do not match; check the configuration
data on the Slave and the Master. See
“Copying the Slave configuration from the
Master configuration”, page 6-4
00FE
DP_SL_ERR_BUS_FAULT
No communication between Master and
Slave, e.g. incorrect slave ID-number
on the Master, Bus interrupted during
data exchange, Master switched off;
Establish cause and rectify
00FF
DP_SL_ERR_FATAL
Hardware error; change PSS(1) DP-S
module or PSS SB 3006 DP-S
2000
DP_SL_NO_ERROR
No error detected
2001
DP_SL_ERR_SLAVE_NOT_
Slave does not respond or is busy;
READY
Reset the module
2002
DP_SL_ERR_DIAG_DATA_
PSS not enabling the DPR or DPR
AREA_NOT_READY
is defective; Change PSS(1) DP-S module
or PSS 3006 DP-S.
2003
DP_SL_ERR_ IN_DATA_
PSS not enabling the DPR or DPR
AREA_NOT_READY
is defective; Change PSS(1) DP-S module
or PSS 3006 DP-S.
2004
DP_SL_ERR_ OUT_DATA_
PSS not enabling the DPR or DPR
AREA_NOT_READY
is defective; Change PSS(1) DP-S module
or PSS 3006 DP-S.
2005
DP_SL_RESET_MODE
A reset has been triggered.
2006
DP_SL_ERR_ILLEGAL_MODE
Invalid mode has been set
2007
DP_SL_ERR_ILLEGAL_
Undefined slave condition; reset or restart
SLAVE_STATE
the module.
INFORMATION
Standard function blocks SB 231 and SB 232 must also be transmitted to
the controller in addition to SB 230. However, parameters do not need to
be set for them, nor do they need to be called up.
NOTICE
The flag range MW 059.00 ... MW 063.16 is reserved for temporary flags.
This range may not be used for global parameters, nor for SB input or
output parameters, otherwise the flags used in the SB will be overwritten.