PROFIBUS-DP-Slave Operating Manual

6-3

Standard Function Blocks

ERR (hex) Key

Cause/Remedy

00FD

DP_SL_ERR_CHK_CFG

Configuration data on Master and Slave
do not match; check the configuration
data on the Slave and the Master. See
“Copying the Slave configuration from the
Master configuration”, page 6-4

00FE

DP_SL_ERR_BUS_FAULT

No communication between Master and
Slave, e.g. incorrect slave ID-number
on the Master, Bus interrupted during
data exchange, Master switched off;
Establish cause and rectify

00FF

DP_SL_ERR_FATAL

Hardware error; change PSS(1) DP-S
module or PSS SB 3006 DP-S

2000

DP_SL_NO_ERROR

No error detected

2001

DP_SL_ERR_SLAVE_NOT_

Slave does not respond or is busy;

READY

Reset the module

2002

DP_SL_ERR_DIAG_DATA_

PSS not enabling the DPR or DPR

AREA_NOT_READY

is defective; Change PSS(1) DP-S module
or PSS 3006 DP-S.

2003

DP_SL_ERR_ IN_DATA_

PSS not enabling the DPR or DPR

AREA_NOT_READY

is defective; Change PSS(1) DP-S module
or PSS 3006 DP-S.

2004

DP_SL_ERR_ OUT_DATA_

PSS not enabling the DPR or DPR

AREA_NOT_READY

is defective; Change PSS(1) DP-S module
or PSS 3006 DP-S.

2005

DP_SL_RESET_MODE

A reset has been triggered.

2006

DP_SL_ERR_ILLEGAL_MODE

Invalid mode has been set

2007

DP_SL_ERR_ILLEGAL_

Undefined slave condition; reset or restart

SLAVE_STATE

the module.

INFORMATION
Standard function blocks SB 231 and SB 232 must also be transmitted to
the controller in addition to SB 230. However, parameters do not need to
be set for them, nor do they need to be called up.

NOTICE
The flag range MW 059.00 ... MW 063.16 is reserved for temporary flags.
This range may not be used for global parameters, nor for SB input or
output parameters, otherwise the flags used in the SB will be overwritten.