Standard function blocks – Pilz ST SB DP S, SW paket PROFIBUS-DP User Manual

Page 34

background image

Standard Function Blocks

6-2

PROFIBUS-DP-Slave Operating Manual

ERR (hex) Key

Cause/Remedy

0003

DP_SL_ERR_SSA_IND

Master attempting to change slave
address; reconfigure Master

0004

DP_SL_ERR_DIAG_LEN

Diagnostic data length is incorrect;
Change data length

0005

DP_SL_ERR_CFG_LEN

Configuration data length is incorrect;
Change length

0006

DP_SL_ERR_PRM_LEN

Parameter data length is incorrect;
Change length

0007

DP_SL_ERR_IO_LEN

Data length is incorrect (inputs or outputs);
Change length

0008

DP_SL_ERR_DP_WD_TIMEOUT Master monitoring has elapsed;

0009

DP_SL_ERR_WRONG_ADRESS Invalid station address has been set;

Set a valid address (0 - 126) on the switch
and in the data block

000A

DP_SL_ERR_IDENT_NR_P

Incorrect ID-number in data block;
Correct ID-number: 2500 hex.

000B

DP_SL_ERR_WRONG_DB_NR

Invalid DB number; select a valid DB

000C

DP_SL_ERR_IO_NULL_PTR

Input and output data length equal zero;
check the configuration data

1000

DP_SL_ERR_SLAVE_NOT_

Slave does not respond or is busy;

READY

Reset the module

1001

DP_SL_ERR_WRONG_SLAVE_

Undefined slave condition; reset or

STATE

restart module

1002

DP_SL_ERR_DIAG_DATA_

Access to DPR denied; reset or restart

AREA_NOT_READY

module

1003

DP_SL_ERR_CFG_DATA_

Access to DPR denied; reset or restart

AREA_NOT_READY

module

00FA

DP_SL_ERR_DPRAM_TIMEOUT PSS not enabling the DPR or DPR

is defective; reset or restart module

00FB

DP_SL_ERR_SET_PRM

Parameter data on Master and Slave do
not match; check the configuration data

00FC

DP_SL_ERR_MASTER_NOT_

Master not available, bus interrupted

READY

when starting the slave