Standard function blocks – Pilz ST SB DP S, SW paket PROFIBUS-DP User Manual
Page 34

Standard Function Blocks
6-2
PROFIBUS-DP-Slave Operating Manual
ERR (hex) Key
Cause/Remedy
0003
DP_SL_ERR_SSA_IND
Master attempting to change slave
address; reconfigure Master
0004
DP_SL_ERR_DIAG_LEN
Diagnostic data length is incorrect;
Change data length
0005
DP_SL_ERR_CFG_LEN
Configuration data length is incorrect;
Change length
0006
DP_SL_ERR_PRM_LEN
Parameter data length is incorrect;
Change length
0007
DP_SL_ERR_IO_LEN
Data length is incorrect (inputs or outputs);
Change length
0008
DP_SL_ERR_DP_WD_TIMEOUT Master monitoring has elapsed;
0009
DP_SL_ERR_WRONG_ADRESS Invalid station address has been set;
Set a valid address (0 - 126) on the switch
and in the data block
000A
DP_SL_ERR_IDENT_NR_P
Incorrect ID-number in data block;
Correct ID-number: 2500 hex.
000B
DP_SL_ERR_WRONG_DB_NR
Invalid DB number; select a valid DB
000C
DP_SL_ERR_IO_NULL_PTR
Input and output data length equal zero;
check the configuration data
1000
DP_SL_ERR_SLAVE_NOT_
Slave does not respond or is busy;
READY
Reset the module
1001
DP_SL_ERR_WRONG_SLAVE_
Undefined slave condition; reset or
STATE
restart module
1002
DP_SL_ERR_DIAG_DATA_
Access to DPR denied; reset or restart
AREA_NOT_READY
module
1003
DP_SL_ERR_CFG_DATA_
Access to DPR denied; reset or restart
AREA_NOT_READY
module
00FA
DP_SL_ERR_DPRAM_TIMEOUT PSS not enabling the DPR or DPR
is defective; reset or restart module
00FB
DP_SL_ERR_SET_PRM
Parameter data on Master and Slave do
not match; check the configuration data
00FC
DP_SL_ERR_MASTER_NOT_
Master not available, bus interrupted
READY
when starting the slave