beautypg.com

Setting parameters – Pilz ST SB DP S, SW paket PROFIBUS-DP User Manual

Page 19

background image

PROFIBUS-DP-Slave Operating Manual

4-7

Setting Parameters

Contents of ID-Byte:

Bit No.

7

6

5

4

3

2

1

0

x

1

x

x

x

x

x

x

Length of data: 0000

... 1111

corresponds to 1 ... 16 words

Input / Output
00

= Special ID-format

01

= PSS output data

10

= PSS input data

11

= PSS input and output data

Data structure: 1: Word, 0: Byte
We recommend you set Bit 6 = 1 (Word)

Consistency: 0: for one word, 1: for the whole data length

The length of the configuration data must be entered in bytes in DW 0813.
The length is 1, if only one byte is used, or two if both bytes of data word
DW 0384 are used.

Examples: Consistency always over the whole data length

DW 0384

1 word output

1101 0000

B

D0

H

00

D0

16 words output

1101 1111

B

DF

H

00

DF

1 word input

1110 0000

B

E0

H

00

E0

16 words input

1110 1111

B

EF

H

00

EF

Input and output, 1 word each

1111 0000

B

F0

H

00

F0

Input and output, 12 words each 1111 1011

B

FB

H

00

FB

1 word output and

1101 0000

B

D0

H

E0

D0

2 words input

1110 0001

B

E0

H

15 words output and

1101 1110

B

DE

H

EF

DE

16 words input

1110 1111

B

EF

H