Setting parameters – Pilz ST SB DP S, SW paket PROFIBUS-DP User Manual
Page 29
PROFIBUS-DP-Slave Operating Manual
4-17
Setting Parameters
Example 5:
2 words input and 1 word output
Configuration byte: C0
Length byte input: C1
Length byte output: C0
Diagnostics:
3 words of internal diagnostic data
1 word of device-related diagnostic data
2 bytes of user-specific diagnostic data
Data word
Contents
Description
DW 0000 - DW 0001
...
Input data
DW 0128
...
Output data
DW 0258
KH 2500
ID-number
DW 0259
KH 0004
Device-related diagnostics
DW 0260
KH xxxx
User-specific diagnostic data
DW 0384
KH C1C0
Configuration data
DW 0385
KH 00C0
DW 0783
KF 10
max_diag_len [Byte]
DW 0795
KH F5
Pre-assigned
DW 0800
KF 1
Slave address [0-126]
DW 0801
KF 0
Transmission sequence
DW 0810
KF 2
Length of input data in words
DW 0811
KF 1
Length of output data in words
DW 0812
KF 5
Length of diagnostic data in words
DW 0813
KF 3
Amount of configuration data in bytes
DW 0814
KF 0
Pre-assigned
DW 0815
KF 0
Pre-assigned