Setting parameters – Pilz ST SB DP S, SW paket PROFIBUS-DP User Manual
Page 21
![background image](https://www.manualsdir.com/files/762823/content/doc021.png)
PROFIBUS-DP-Slave Operating Manual
4-9
Setting Parameters
ID-Byte:
Bit No.
7
6
5
4
3
2
1
0
x
x
0
0
x
x
x
x
Length of manufacturer-specific data
ID-code
00
= Reserved
01
= 1 length byte for PSS output data follows
10
= 1 length byte for PSS input data follows
11
= 1 length byte for PSS input data and one length byte for
PSS output data follow
INFORMATION
Manufacturer-specific data is not pre-assigned by Pilz. Users may enter
their own data - please refer to the standard.
If no data is to be entered, enter the value 0 in Bits 0 ... 3 .
Length-Byte:
Bit No.
7
6
5
4
3
2
1
0
x
1
x
x
x
x
x
x
Length of data: 000000 ... 111111 corresponds to
1 ... 64 words
Data structure: 1: Word, 0: Byte
We recommend you set Bit 6 = 1 (Word)
Consistency: 0: for one word, 1: for the whole data length
INFORMATION
The amount of configuration data must be entered in Bytes in DW 0813.