Setting Parameters
4-16
PROFIBUS-DP-Slave Operating Manual
Example 4 :
100 words input and output
Configuration byte: C0
Length byte input (64 words): FF
Length byte output (64 words): FF
Configuration byte:
C0
Length byte input (36 words): E3
Length byte output (36 words): E3
Diagnostics:
3 words of internal diagnostic data
1 word of device-related diagnostic data
50 bytes of user-specific diagnostic data
Data word
Contents Description
DW 0000 - DW 0099
...
Input data
DW 0128 - DW 0227
...
Output data
DW 0258
KH 2500 ID-number
DW 0259
KH 0052 Device-related diagnostics
DW 0384
KH FFC0 Configuration data
DW 0385
KH C0FF
DW 0386
KH E3E3
DW 0783
KF 58
max_diag_len [Byte]
DW 0795
KH F5
Pre-assigned
DW 0800
KF 1
Slave address [0-126]
DW 0801
KF 0
Transmission sequence
DW 0810
KF 100
Length of input data in words
DW 0811
KF 100
Length of output data in words
DW 0812
KF 29
Length of diagnostic data in words
DW 0813
KF 6
Amount of configuration data in bytes
DW 0814
KF 0
Pre-assigned
DW 0815
KF 0
Pre-assigned