PROFIBUS-DP-Slave Operating Manual

4-13

Setting Parameters

Data word Type Contents
DW 0813

KF

Amount of configuration data 1- 244 [Byte]
(DW 0384ff)

DW 0814

KF

Only 0 is permitted

DW 0815

KF

Only 0 is permitted

DW 0816...DW 1023

Reserved

NOTICE
The data length may be a maximum of 1472 Bytes. The maximum data
length is calculated as follows:

3 x length of the input data

+

3 x length of the output data

+

2 x length of the diagnostic data

+

4 x length of the configuration data

+

120 Byte

Examples

Example 1:
12 words input and output: configuration byte FB

H

;

Length of configuration data: 1 Byte
Diagnostics: 3 words of internal diagnostic data

1 word of device-related diagnostic data

Data word

Contents

Description

DW 0000 - DW 0011

...

Input data

DW 0128 - DW 0139

...

Output data

DW 0258

KH 2500

ID-number

DW 0259

KH 0002

Device-related diagnostics

DW 0384

KH 00FB Configuration data

DW 0783

KF 10

max_diag_len [Byte]

DW 0795

KH F5

Pre-assigned

DW 0800

KF 1

Slave address [0-126]

DW 0801

KF 0

Transmission sequence

DW 0810

KF 12

Length of input data in words

DW 0811

KF 12

Length of output data in words

DW 0812

KF 4

Length of diagnostic data in words

DW 0813

KF 1

Amount of configuration data in bytes

DW 0814

KF 0

Pre-assigned

DW 0815

KF 0

Pre-assigned