Standard function block sb 230, Intended use – Pilz ST SB DP S, SW paket PROFIBUS-DP User Manual
Page 12

Intended Use
3-2
PROFIBUS-DP-Slave Operating Manual
Standard function block SB 230
SB 230 may be used with the following functions and parameters:
• PROFIBUS-DP connection
• To trigger a slave reset
• To trigger static diagnostics
• Permitted data lengths:
Input data: 0 ... 108 words (set via parameters)
Output data: 0 ... 108 words (set via parameters)
Diagnostic data: 4 ... 35 words (set via parameters)
Configuration data: 1 ... 244 bytes (set via parameters)
Please note that the overall data length may be a max. of 1472 Bytes.
Information on calculating the data length can be found in the section
entitled "Setting data blocks".
INFORMATION
SB 230 must be called up in the user program as part of each cycle.