Technical details, 8technical details, 1 technical details – Pilz PSSu E S 2DOR 10 User Manual
Page 34

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
8-1
8.1
Technical details
8
Technical details
8
8000
Technical details
Technical details
8-
8.1
Technical details
8100
Technical details
8-
][Technische Daten PSSu Digitale E/A/K
Technical details
Application range
Standard
Module's device code
0403h
Number of ST output bits
2
Support in system environment A
yes
from ST firmware version for other head modules
16
from ST firmware version PSSu H S PN
2
from ST firmware version PSSu WR S IDN
9
Support in system environment B
yes
from head module ST firmware version
1.7.0
Electrical data
Internal supply voltage (module supply)
Supply voltage range of module supply
4.8 - 5.4 V
Module's current consumption
19 mA
Module's power consumption
0.09 W
Periphery's supply voltage (periphery supply)
Voltage range
16.8 - 30.0 V
Module's current consumption with no load
60 mA
Module's power consumption with no load
1.50 W
Max. power dissipation of the module
2.50 W
Outputs
Number of relay outputs
2
Contact material
AgCuNi
External contact fuse protection (I
K
= 1 kA) to EN 60947-5-1
quick
10 A
slow
6 A
Potential isolation between relay contact and periphery
supply
4900 V (safe separation)
Potential isolation between relay contact and module sup-
ply
4900 V (safe separation)
Potential isolation between relay contact and C-rail
3050 V (basic insulation)
Potential isolation between relay contact 1 and relay con-
tact 2
4900 V (safe separation)
Utilisation category in accordance with EN 60947-4-1
Relay contacts: AC1 at 250 V
I
min
: 10.00 mA , I
max
: 10.0 A
P
max
: 2400 VA
Relay contacts: DC1 at 24 V
I
min
: 10.00 mA , I
max
: 10.0 A
P
max
: 240 W
Utilisation category in accordance with EN 60947-5-1
Relay contacts: AC15 at 240 V
I
max
: 6.0 A
Relay contacts: DC13 at 24 V (6 cycles/min)
I
max
: 2.0 A
Switching capability in accordance with UL 508
240 V AC G. P.
4.0 A
24 V DC G. P. Resistive
4.0 A
24 V DC Pilot Duty
3.0 A
Permitted loads
inductive, resistive
Times
Max. processing time for relay output when signal changes
from "1" to "0"
25 ms
Max. processing time for relay output when signal changes
from "0" to "1"
15 ms