Function description, Module features, 1 integrated protection mechanisms – Pilz PSSu E S 2DOR 10 User Manual
Page 17: 2 function description, 4function description, 1 module features

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
4-1
4.1
Module features
4
Function description
4
4000
Function description
Function description
4-
4.1
Module features
4100
Module features
4-
4.1.1
Integrated protection mechanisms
Integrated protection mechanisms
4-
][Schutzmechanismen E/A-Module
When the PSSu E F PS1(-T) is used to supply the system, the module
supply is buffered for 20 ms if the supply voltage is interrupted.
][Schutzmechanismen ST-Ausgang Relais
The module has the following protection mechanisms:
Safe separation between both relay contacts (see Technical details)
Safe separation between both relay contacts and the periphery sup-
ply as well as the module supply, in accordance with DIN VDE 0110
overvoltage category 2 in a protected industrial network
Temperature monitoring
The module provides the following diagnostic data:
Start-up error
Configuration error
ST communication error
Bus termination error
Temperature error: too warm
Temperature error: too hot
4.1.2
Function description
Function description
4-
][Funktionsbeschreibung Module Supply
Module supply
The module supply provides the module with voltage.
][Funktionsbeschreibung_Aus Relais
Outputs
The head module sets the output status via the module bus.
][Funktionsbeschreibung Derating
The relationship between the load current and the operating temper-
ature is illustrated in the following derating diagram. The operating
point should be below the characteristic curve.
][Funktionsdiagramm S 2DOR 10