1 safety characteristic data, Safety characteristic data – Pilz PSSu E F DI OZ 2 User Manual
Page 34

Technical details
Operating Manual PSSu E F DI OZ 2(T)(R)
21328EN05
34
Mechanical data
312220
314220
315220
Dimensions
Height
76,0 mm
76,0 mm
76,0 mm
Width
12,6 mm
12,6 mm
12,6 mm
Depth
60,2 mm
60,2 mm
60,2 mm
Weight
44 g
46 g
46 g
Mechanical coding
Type
G
G
G
Colour
Yellow
Yellow
Yellow
The standards current on 200910 apply.
8.1
Safety characteristic data
Unit
Operating
mode
EN ISO
138491: 2008
PL
EN ISO
138491: 2008
Category
EN IEC 62061
SIL CL
EN IEC 62061
PFH
D
[1/h]
EN ISO
138491: 2008
T
M
[year]
Logic
Input
Digital inputs
1channel
PL d
Cat. 2
SIL CL 2
9,10E09
20
Digital inputs
2channel
PL e
Cat. 3
SIL CL 3
3,10E09
20
Digital inputs
1ch., pulsed
light barrier
PL e
Cat. 4
SIL CL 3
2,91E09
20
Output
SC outputs (2
pole)
2channel
PL e
Cat. 4
SIL CL 3
1,37E09
20
If the module is operated at an ambient temperature above 60° C, the values stated in the
table for PFH
D
and PFD will need to be doubled when a safety function is calculated.
All the units used within a safety function must be considered when calculating the safety
characteristic data.
INFORMATION
A safety function's SIL/PL values are not identical to the SIL/PL values of
the units that are used and may be different. We recommend that you use
the PAScal software tool to calculate the safety function's SIL/PL values.