beautypg.com

3 connecting the module, 4 function test during commissioning, Connecting the module – Pilz PSSu E F DI OZ 2 User Manual

Page 26: Function test during commissioning

background image

Wiring

Operating Manual PSSu E F DI OZ 2(­T)(­R)
21328­EN­05

26

6.3

Connecting the module

Output circuit

Without C­rail

Single­channel operation

Redundant actuator

11

12

13

14

21

22

23

24

O0+

I0

O0-

n. c.

n.c.

n.c.

T0

T0

L1

K1

K2

M

K1

K2

K1

K2

RFK

Dual­channel operation

Redundant actuator

11

12

13

14

21

22

23

24

O0+

I0

O0-

n. c.

n.c.

n.c.

T0

T0

K1

11

12

13

14

21

22

23

24

O0+

I0

O0-

n. c.

n.c.

n.c.

T0

T0

K2

L1

K1

K2

M

K1

K2

RFK

6.4

Function test during commissioning

An error must be simulated for each safety­related output during commissioning: The anti­
cipated error reaction must occur when an output has a short circuit to a supply voltage.

INFORMATION

The short circuit test must be performed on the load and not on the output
terminal.

This manual is related to the following products: