Pilz PSSu E F DI OZ 2 User Manual
Page 14

Function description
Operating Manual PSSu E F DI OZ 2(T)(R)
21328EN05
14
Open circuit detection
}
The module will detect an open circuit between outputs O0+ and O0.
}
The result of open circuit detection is signaled to the head module via a virtual input.
The result is available within the user program:
}
No open circuit detected: Status bit set
–
Open circuit detected: Status bit not set
}
Loads over 3 kOhm may mistakenly be detected as an open circuit.
Characteristic: Output capacitance C dependent on load current I
1
2
3
4
5
0
0,2
0,4
0,6
0,8
1
1,2
1,4
1,6
1,8
2
C [µF]
I [A]
Derating diagram ( PSSu E F DI OZ 2(T)(R)): Permitted ambient temperature T de
pendent on load current I
20
40
60
80
100
0
1
2
T [°C]
I [A]
1,4
1,2
1,6
1,8
0,4
0,2
0,6
0,8
This manual is related to the following products: