Page 15: 1 pssu assignment in system environment a, 1 dual-pole output, 2 input and test pulse output, Integrated protection mechanisms, Reaction times, Configuration, Pssu assignment in system environment a

Function description
Operating Manual PSSu E F DI OZ 2(T)(R)
21328EN05
15
4.1.2
Integrated protection mechanisms
When the PSSu E F PS1(T) is used to supply the system, the module supply is buffered
for 20 ms if the supply voltage is interrupted.
The module has the following protection mechanisms:
}
Cyclical output tests
}
Tests for shorts across the output
}
Test pulse signals are always buffered for 20 ms.
The module provides the following diagnostic data:
}
Startup error
}
Configuration error
}
FS communication error
}
Bus termination error
}
Temperature error: too warm
}
Temperature: too hot
}
Output error
}
Test pulse error
}
Input error
4.1.3
Reaction times
Information on the reaction times of the inputs and outputs can be found in the PSSuniver
sal System Description.
4.2
Configuration
4.2.1
PSSu assignment in system environment A
4.2.1.1
Dualpole output
Functions for the FS outputs of a PSSu are defined in the PSSuniversal Configurator on the
PSS WINPRO system software:
}
Read access through the standard bus system (configured per module):
“R” configuration
}
Read/write access through the standard bus system (configured per output):
"&" configuration (local enable principle)
}
Optimisation of ST process image by combining adjacent bits of the same type.
“*” configuration
4.2.1.2
Input and test pulse output
Functions for the FS inputs of a PSSu are defined in the PSSuniversal Configurator on the
PSS WINPRO system software:
}
Read access through the standard bus system (configured per module):
Configuration "R"
}
Allocation of a test pulse to an input (configured per input):