Page 23: Section 6, Wiring, General wiring guidelines, Mechanical connection of the base modules, 6wiring, Din 5264-a

background image

Wiring

Operating Manual PSSu E F 4DO 0.5(­T)(­R)
21316­EN­05

23

6

Wiring

6.1

General wiring guidelines

Please note:

}

If short circuits occur between the cable from the output to the load and a supply line, it
will no longer be possible to switch off the load. Possible remedies:

}

Use separate multicore cable for supply voltages

Use dual actuators, e.g. two contactors in series

Use an additional shutdown device such as a main contactor

}

Use appropriate wiring to exclude short circuits between the outputs!

}

With single­channel operation for applications up to Category 3 in accordance with EN
954­1: use a feedback loop!

}

When used for Category 4 applications in accordance with EN 954­1: connect two actu­
ators connected in series to two different outputs!

}

The actuators may be connected using unshielded cables.

}

The outputs do not need suppression for inductive loads.

}

Use copper wiring.

}

The terminal configuration as stated on the front plate applies for base modules with C­
rail. The terminal configuration as stated in the technical documentation applies for all
other base modules.

6.1.1

Mechanical connection of the base modules

Procedure:

}

Use a flat blade screwdriver (DIN 5264­A)!

DIN 5264-A

}

Strip the wire back 8 mm.

}

If necessary, label the connection level with a colour marker [3].

}

Base module with screw terminals:

Use a screwdriver to loosen the screw on the screw terminal [1]

Insert the stripped cable into the round fixing hole [2], as far as it will go.

Tighten up the screw on the screw terminal.

Check that the cable is firmly seated.