beautypg.com

4 function description, 1 module features, 1 function description – Pilz PSSu E F 4DO 0.5 User Manual

Page 13: Section 4, Function description, Module features, 4function description

background image

Function description

Operating Manual PSSu E F 4DO 0.5(­T)(­R)
21316­EN­05

13

4

Function description

4.1

Module features

4.1.1

Function description

Module supply

}

The module supply provides the module with voltage.

Signals at the output

}

“0” signal (0 V) at the output:

}

Output is high impedance

No current to the load

}

“1” signal (+24 V) at the output:

}

Output is low impedance

Current is supplied to the load

Periphery supply

}

The module routes the periphery supply from the module bus to the base module ter­
minals.

}

The periphery supply is used to supply the outputs.

Outputs

}

The head module sets the output status via the module bus.

}

The max. capacity at an output depends on the load (see characteristic). Connecting a
higher capacity may lead to an error.

}

Operation with electronic contactors has not been tested and may lead to errors.
Please contact our Customer Support team if you are using electronic contactors.

Output test

}

Outputs that are switched on are checked via regular off tests.

}

Test pulses for outputs that are switched on: see Technical Details

Outputs that are switched on are switched off for the duration of the test pulse.

The load must not switch off because of the test.

}

Outputs that are switched off are checked via regular on tests.

}

Test pulses for outputs that are switched off: see Technical Details

Outputs that are switched off are switched on for the duration of the test pulse.

The load must not switch on because of the test.

Excluding individual outputs from the output test:

}

If a plant is particularly sensitive to the test pulses, they may be switched off for indi­
vidual outputs.

}

The test must be replaced by other measures, depending on the safety requirement.

}

When test pulses are switched off:

}

The correct switch status is always checked.