7 operation, 1 messages, Section 7 – Pilz PSSu E F 4DI User Manual
Page 28: Operation, Messages, 7operation

Operation
Operating Manual PSSu E F 4DI(T)(R)
21310EN05
28
7
Operation
7.1
Messages
A module error is displayed via the "Err" LED (see section entitled "Display elements"), sig
nalled to the head module and then entered in the head module's
}
Error stack, with PSSu in system environment A
}
Diagnostic log, with PSSu in system environment B.
The module can detect the following errors:
Module error
Explanation
Remedy
Startup error
Error as the PSSu system starts
up
Change faulty module.
Configuration error
Incorrect module type configured.
The configured hardware registry
does not match the actual hard
ware registry.
FS communication error
Error during FS communication
Change faulty module.
Bus termination error
There is no terminating plate or
there is a bad contact with the
module bus.
Install a terminating plate with in
tegrated end bracket or insert the
base modules together correctly.
Temperature error: too warm
Ambient temperature too high:
Error stack entry/diagnostic log
entry
Ensure there is sufficient ventila
tion in the control cabinet or pre
vent overload.
Error in the feedback loop
FS input detects an error in the
feedback loop or FS input is de
fective.
Check FS input, check the config
uration of the feedback loop,
check the signals, or check the
wiring and contacts.
Input error
Error during the cyclical input test.
Possible cause: Input defective.
Change faulty module.
Test pulse error
Possible causes: Short circuit
between a test pulse and a supply
voltage, or a defective module.
Rectify the short circuit or change
the faulty module.