3 safety, 1 intended use, Section 3 – Pilz PSSu E F 4DI User Manual
Page 10: Safety, Intended use, 3safety

Safety
Operating Manual PSSu E F 4DI(T)(R)
21310EN05
10
3
Safety
3.1
Intended use
The module may be used for failsafe applications in system environment A and B (automa
tion system PSS 4000).
The modules PSSu E F 4DI and PSSu E F 4DIT may be used as a safety component in
accordance with the Lifts Directive 95/16/EC, EN 811, EN 812 and EN 1151.
The programmable safety system should be installed in a protected environment that meets
at least the requirements of pollution degree 2. Example: Protected inside space or control
cabinet with protection class IP54 and corresponding air conditioning.
The module meets the requirements of EN IEC 61508 up to SIL 3.
It provides type 1 failsafe inputs in accordance with IEC 611312.
The module PSSu E F 4DIT is suitable for use where there are increased environmental
requirements (see Technical Details).
The module PSSu E F 4DIR is suitable for use where there are increased environmental
requirements demanded by railway applications (see Technical Details).
Intended use includes making the electrical installation EMCcompliant. Please refer to the
guidelines stated in the "PSSuniversal Installation Manual". The module is designed for use
in an industrial environment. It is not suitable for use in a domestic environment, as this can
lead to interference.
The following is deemed improper use in particular:
}
Any component, technical or electrical modification to the module
}
Use of the module outside the areas described in this manual
}
Any use of the module that is not in accordance with the technical details.
INFORMATION
The module is supported by
}
PSSuniversal Configurator and PSSuniversal Assistant from Version
1.4.0 (base type, Ttype)
}
PAS4000 from Version 1.1.1 (base type, Ttype)
}
PAS4000 from Version 1.5.0 (Rtype)
– We recommend that you always use the latest version (download
from www.pilz.de).
The PSSu E F 4DI module may be used in conjunction with the following base modules:
}
PSSu BP 1/8S
}
PSSu BP 1/8C
}
PSSu BP 1/12S
}
PSSu BP 1/12C
}
PSSu BPC1 1/12S
}
PSSu BPC1 1/12C