2 configuration, 1 pssu assignment in system environment a, 1 addresses in the process image – Pilz PSSu E F 4DI User Manual
Page 14: 2 pssu assignment in system environment b, Configuration, Pssu assignment in system environment a, Addresses in the process image, Pssu assignment in system environment b

Function description
Operating Manual PSSu E F 4DI(T)(R)
21310EN05
14
4.2
Configuration
4.2.1
PSSu assignment in system environment A
Functions for the FS inputs of a PSSu are defined in the PSSuniversal Configurator on the
PSS WINPRO system software:
}
Read access through the standard bus system
(configured per module):
“R” configuration
}
Allocation of a test pulse output to an input
(configured per input)
}
Optimisation of ST process image by combining adjacent bits of the same type.
“*” configuration
INFORMATION
The PSSuniversal Configurator on the PSS WINPRO system software
must be used to define the I/OGroups to which FS inputs and outputs be
long (SafetyBUS p). The PSSu can be divided into sections A and B for this
purpose. All the FS inputs on a PSSu always belong to section B.
Section A and section B on a PSSu may belong to different I/OGroups.
Further information on configuration is available in the PSSuniversal Configurator's online
help.
4.2.1.1
Addresses in the process image
The module occupies 4 consecutive bit addresses in the process image. The process im
age in which the inputs are shown depends on the configuration.
Configuration
SafetyBUS p
Standard bus system
FSPII
STPII
STPIO
None
4 Bit
(e. g.: 32.00 … 32.03)
Read ST (“R”)
4 Bit
4.2.2
PSSu assignment in system environment B
Data access is via predefined I/O data types:
I/O data name
I/O data type
I/O data element
Meaning
I0(11), I1(21), I2(14),
I3(24)
FS_I_DI
Data: SAFEBOOL
Input data I0 ... I3