8technical details, 1 technical details – Pilz PSSu H SB CAN User Manual
Page 40

8.1
Technical details
8
Technical details
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
8-2
SI-Kennzahlen_PSSu_Kopf
Si_Kennzahlen_Erläuterung
All the units used within a safety function must be considered when cal-
culating the safety characteristic data.
Technische Daten_Satz Normen
Environmental data
Climatic suitability
EN 60068-2-14, EN 60068-2-1, EN 60068-2-2,
EN 60068-2-30, EN 60068-2-78
Ambient temperature
0 - 60 °C
-40 - 70 °C coated version (-T)
Storage temperature
-25 - 70 °C
-40 - 70 °C coated version (-T)
Climatic suitability in accordance with EN 60068-2-78
93 % r. h. at 40 °C
Condensation
no
yes coated version (-T)
Max. operating height above sea level
5000 m coated version (-T)
EMC
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4,
EN 61000-4-5, EN 61000-4-6, EN 61000-6-2,
EN 61000-6-4
Vibration to EN 60068-2-6
Frequency
10 - 150 Hz
Max. acceleration
1g
Shock stress
EN 60068-2-27
15g
11 ms
EN 60068-2-29
10g
16 ms
Protection type
Mounting (e.g. cabinet)
IP54
Housing
IP20
Airgap creepage in accordance with EN 60664-1
Overvoltage category
II
Pollution degree
2
Mechanical data
Housing material
Front
PC
Bottom
PC
Dimensions
Height
128.4 mm
Width
75.2 mm
Depth
79.4 mm
Weight
170 g
Safety characteristic data
Unit
Operating mode
EN ISO 13849-1
PL
EN 954-1
Category
EN IEC 62061
SIL CL
PFH [1/h]
t
M
[year]
Logic
---
PL e (Cat. 4)
Cat. 4
SIL CL 3
2.88E-09
20