Technical details, 8technical details, 1 technical details – Pilz PSSu H SB CAN User Manual
Page 39

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
8-1
8.1
Technical details
8
Technical details
8
8000
Technical details
Technical details
8-
8.1
Technical details
8100
Technical details
8-
][Technische Daten PSSu Kopf SBUS+ST-BUS mZust
Technical details
Application range
Standard/Failsafe
Maximum achievable category in accordance with
EN 954-1
4
Maximum achievable SIL value
SIL3
Module's device code
0224h
Electrical data
Internal supply voltage
Supply voltage range of module supply
4.9 - 5.1 V
Current and power consumption from module supply
Module's current consumption without FO connection
320 mA
FO connection's current consumption
120 mA
Module's power consumption without FO connection
1.60 W
FO connection's power consumption
0.60 W
Max. power dissipation of the module
1.60 W
Potential isolation between module supply and CANopen 700 V
Potential isolation between module supply and
SafetyBUS p
700 V
SafetyBUS p
Application range
Failsafe applications
Device address
32d ... 95d
Max. transmission rate
500 kBit/s
Cable runs
3,500 m
Transmission type
differential two-wire cable
Connection
Male 9-pin D-SUB connector
CANopen
Application range
Standard applications
Failsafe applications with local enable principle
Device type
Slave
Station address
1 .. 127d
Set via
DIP switch
Maximum data length of the fieldbus interface: Input
64 Byte
Maximum data length of the fieldbus interface: Output
64 Byte
Maximum data length of the fieldbus interface: Diagnostics 5 Byte
Transmission rates
1 MBit/s, 10 kbit/s, 100 kBit/s, 125 kBit/s, 20 kbit/s,
250 kBit/s, 50 kbit/s, 500 kBit/s, 800 kbit/s
Set via
automatic/DIP switch
Connection
Male 9-pin D-SUB connector
Protocol
CANopen Standard 4,0
Operating modes
Slave Mode
Certification
CiA
Description file
PSSuCO.eds
Manufacturer's ID
0189h
USB
Connection
Mini-B connector