Operation

Operating Manual PNOZ m ES Profibus
1002698­EN­03

18

7

Operation

7.1

Messages

When the supply voltage is switched on, the PNOZmulti safety system copies the configur­
ation from the chip card.

The LEDs "POWER","DIAG", "FAULT", "IFAULT" and "OFAULT" light up on the base unit.

The expansion module PNOZ m ES Profibus is configured and started automatically. The
"ONLINE" and "OFFLINE" LEDs indicate the status of the PNOZ m ES Profibus on
PROFIBUS­DP.

If the expansion module PNOZ m ES Profibus does not receive a configuration from the
base unit for a period of 30 s, the expansion module PNOZ m ES Profibus connects to
PROFIBUS­DP and "ONLINE" status is displayed on PROFIBUS­DP. The error message
"No Connection with Base Module" is sent to the Master.

7.1.1

Display elements for device diagnostics

Legend:

LED on

LED flashes

LED off

LED

Meaning

POWER

Supply voltage is present

Supply voltage is not present

ONLINE

PNOZ m ES Profibus Online, data exchange is possible

Master has sent the telegram "Global Control Clear". Virtual input bits i0 ...
i127 are set to "0".

PNOZ m ES Profibus Not online

OFFLINE

PNOZ m ES Profibus Offline, data exchange is not possible

PNOZ m ES Profibus Not offline