beautypg.com

1 safety characteristic data, Safety characteristic data – Pilz PNOZ m EF Multi Link User Manual

Page 20

background image

Technical details

Operating Manual PNOZ m EF Multi Link
1003018­EN­02

20

The standards current on 2013­01 apply.

8.1

Safety characteristic data

Operating
mode

EN ISO
13849­1:
2008

PL

EN ISO
13849­1:
2008

Category

EN IEC
62061

SIL CL

EN IEC
62061

PFH

D

 [1/h]

IEC 61511

SIL

IEC 61511

PFD

EN ISO
13849­1:
2008

T

M

 [year]

PL e

Cat. 4

SIL CL 3

8,82E­09

SIL 3

3,86E­05

20

All the units used within a safety function must be considered when calculating the safety
characteristic data.

INFORMATION

A safety function's SIL/PL values are not identical to the SIL/PL values of
the units that are used and may be different. We recommend that you use
the PAScal software tool to calculate the safety function's SIL/PL values.