Operation

Operating Manual PNOZ m EF Multi Link
1003018­EN­02

17

7.2

Fault detection

Each base unit contains information about

}

its own link module (in order, defective, no supply voltage)

}

the status of the connection (yes, no)

}

the operating status of the connected base unit (RUN, STOP)

When the connection is interrupted, the base units switch the virtual inputs to zero. The
base units remains in a RUN condition.

Defective link module:

}

The corresponding base unit switches to a STOP condition. The virtual outputs on the
link module are set to zero.

}

The connected base unit remains in a RUN condition.