Commissioning

Operating Manual PNOZ m EF Multi Link
1003018­EN­02

14

6

Commissioning

6.1

Wiring

The wiring is defined in the circuit diagram of the PNOZmulti Configurator.

Note:

}

Information given in the "Technical details" must be followed.

}

The power supply must meet the regulations for extra low voltages with protective sep­
aration.

}

2 connection terminals are available for each of the supply connections 24 V and 0 V.
This means that the supply voltage can be looped through several connections. The
current at each terminal may not exceed 3 A.

}

The max. cable length between two link modules on a connection with one link module

PNOZ ml1p 

PNOZ ml1p from V2.0, PNOZ mml1p, PNOZ m EF Multi Link: 1000 m

}

Connect the inputs and outputs from two link modules with 4­core shielded cable. The
cables must be twisted in pairs (see "Preparing for operation").

}

Note the crossover cabling, e.g. CA+ with CB+.

}

The cables must be classified into a minimum of Category 5 in accordance with ISO/
IEC 11801.

CAUTION!

Only connect and disconnect the expansion module when the supply
voltage is switched off.

6.2

Connection

RJ45 socket

8­pin

PIN

Layout

8 1

1

CA+

2

CA­

3

CB+

4

n.c.

5

n.c.

6

CB­

7

n.c.

8

n.c.

Shield

CGround