Pilz PZE X4VP 0,5/24VDC 4n/o fix User Manual
Page 15
PZE X4VP
Operating Manual PZE X4VP
1003202EN08
15
Relay outputs
787580
787581
787582
787583
Contact fuse protec
tion external,
delayed safety con
tacts
Max. melting in
tegral
66 A²s
66 A²s
66 A²s
66 A²s
Blowout fuse,
quick
6 A
6 A
6 A
6 A
Blowout fuse,
slow
4 A
4 A
4 A
4 A
Blowout fuse gG 6 A
6 A
6 A
6 A
Circuit breaker,
24 V AC/DC,
characteristic B/C 4 A
4 A
4 A
4 A
Contact material
AgCuNi + 0,2 µm
Au
AgCuNi + 0,2 µm
Au
AgCuNi + 0,2 µm
Au
AgCuNi + 0,2 µm
Au
Conventional
thermal current
while loading sev
eral contacts
787580
787581
787582
787583
Ith per contact at UB
DC
Conv. therm. cur
rent with 1 con
tact
6,00 A
6,00 A
6,00 A
6,00 A
Conv. therm. cur
rent with 2 con
tacts
5,00 A
5,00 A
5,00 A
5,00 A
Conv. therm. cur
rent with 3 con
tacts
4,50 A
4,50 A
4,50 A
4,50 A
Conv. therm. cur
rent with 4 con
tacts
4,00 A
4,00 A
4,00 A
4,00 A
Times
787580
787581
787582
787583
Delay time tv
0,50 s
1,00 s
2,00 s
3,00 s
Time accuracy
50 %/+50 %
50 %/+50 %
50 %/+50 %
50 %/+50 %
Supply interruption
before deenergisa
tion
20 ms
20 ms
20 ms
20 ms
Environmental data 787580
787581
787582
787583
Climatic suitability
EN 60068278
EN 60068278
EN 60068278
EN 60068278
Ambient temperat
ure
Temperature
range
10 55 °C
10 55 °C
10 55 °C
10 55 °C
Storage temperature
Temperature
range
40 85 °C
40 85 °C
40 85 °C
40 85 °C
EMC
EN 6094751, EN
6100062
EN 6094751, EN
6100062
EN 6094751, EN
6100062
EN 6094751, EN
6100062