PZE X4

Operating Manual PZE X4
1003199­EN­08

9

}

Open circuit, short circuit or earth fault ( e.g. in the input circuit)

Dimensions in mm

Technical details

General

774585

Approvals

CCC, CE, GOST, TÜV, cULus Listed

Electrical data

774585

Supply voltage

Voltage

24 V

Kind

DC

Voltage tolerance

­15 %/+10 %

Output of external power supply (DC)

2,5 W

Residual ripple DC

20 %

Continuous duty

100 %

Max. inrush current impulse

Current pulse, input circuit

2,00 A

Pulse duration, input circuit

2,0 ms

Max. overall cable resistance Rlmax

Single­channel at UB DC

30 Ohm

Voltage at

Input circuit DC

24,0 V

Current at

Input circuit DC

95,0 mA

Number of output contacts

Safety contacts (N/O), instantaneous

4

Inputs

774585

Number

1