beautypg.com

Pilz PZE X4 24VDC 4n/o User Manual

Page 10

background image

PZE X4

Operating Manual PZE X4
1003199­EN­08

10

Relay outputs

774585

Max. short circuit current IK

1 kA

Utilisation category

In accordance with the standard

EN 60947­4­1

Safety contacts, AC1 at

240 V

Max. current

6,0 A

Min. current

0,01 A

Max. power

1500 VA

Safety contacts, DC 1 at

24 V

Max. current

6,0 A

Min. current

0,01 A

Max. power

150 W

Utilisation category

In accordance with the standard

EN 60947­5­1

Safety contacts, AC15 at

230 V

Max. current

5,0 A

Safety contacts DC13 (6 cycles/min) at

24 V

Max. current

5,0 A

Utilisation category in accordance with UL

Voltage

240 V AC G.U. (same polarity)

With current

6,0 A

Voltage

24 V DC G. U.

With current

6,0 A

Pilot Duty

R300

Contact fuse protection external, safety contacts

In accordance with the standard

EN 60947­5­1

Max. melting integral

260 A²s

Blow­out fuse, quick

10 A

Blow­out fuse, slow

6,00 A

Blow­out fuse, gG

10 A

Circuit breaker, 24V AC/DC, characteristic B/C

6 A

Contact material

AgCuNi + 0,2 µm Au

Conventional thermal current while loading sev­
eral contacts

774585

Ith per contact at UB DC

Conv. therm. current with 1 contact

6,00 A

Conv. therm. current with 2 contacts

6,00 A

Conv. therm. current with 3 contacts

5,00 A

Conv. therm. current with 4 contacts

4,00 A

Times

774585

Switch­on delay

With automatic start after power on typ.

30 ms

With automatic start after power on max.

50 ms