Pilz PZE X4 24VDC 4n/o User Manual
Page 11

PZE X4
Operating Manual PZE X4
1003199EN08
11
Times
774585
Delayon deenergisation
With ESTOP typ.
30 ms
With ESTOP max.
50 ms
With power failure typ.
30 ms
With power failure max.
50 ms
Supply interruption before deenergisation
20 ms
Environmental data
774585
Climatic suitability
EN 60068278
Ambient temperature
Temperature range
10 55 °C
Storage temperature
Temperature range
40 85 °C
EMC
EN 6094751, EN 6100062
Vibration
In accordance with the standard
EN 6006826
Frequency
10,0 55,0 Hz
Amplitude
0,35 mm
Airgap creepage
In accordance with the standard
EN 609471
Overvoltage category
III
Pollution degree
2
Rated insulation voltage
250 V
Rated impulse withstand voltage
6,00 kV
Protection type
Mounting area (e.g. control cabinet)
IP54
Housing
IP40
Terminals
IP20
Mechanical data
774585
Mounting position
Any
Mechanical life
10,000,000 cycles
Material
Bottom
PPO UL 94 V0
Front
ABS UL 94 V0
Top
PPO UL 94 V0
Conductor cross section with screw terminals
1 core flexible
0,20 4,00 mm², 24 10 AWG
2 core with the same cross section, flexible with
crimp connectors, no plastic sleeve
0,20 2,50 mm², 24 14 AWG
2 core with the same cross section, flexible without
crimp connectors or with TWIN crimp connectors
0,20 2,50 mm², 24 14 AWG
Torque setting with screw terminals
0,50 Nm
Connection type
Screw terminal
Mounting type
Fixed