beautypg.com

Pilz PZE X4 24VDC 4n/o User Manual

Page 11

background image

PZE X4

Operating Manual PZE X4
1003199­EN­08

11

Times

774585

Delay­on de­energisation

With E­STOP typ.

30 ms

With E­STOP max.

50 ms

With power failure typ.

30 ms

With power failure max.

50 ms

Supply interruption before de­energisation

20 ms

Environmental data

774585

Climatic suitability

EN 60068­2­78

Ambient temperature

Temperature range

­10 ­ 55 °C

Storage temperature

Temperature range

­40 ­ 85 °C

EMC

EN 60947­5­1, EN 61000­6­2

Vibration

In accordance with the standard

EN 60068­2­6

Frequency

10,0 ­ 55,0 Hz

Amplitude

0,35 mm

Airgap creepage

In accordance with the standard

EN 60947­1

Overvoltage category

III

Pollution degree

2

Rated insulation voltage

250 V

Rated impulse withstand voltage

6,00 kV

Protection type

Mounting area (e.g. control cabinet)

IP54

Housing

IP40

Terminals

IP20

Mechanical data

774585

Mounting position

Any

Mechanical life

10,000,000 cycles

Material

Bottom

PPO UL 94 V0

Front

ABS UL 94 V0

Top

PPO UL 94 V0

Conductor cross section with screw terminals

1 core flexible

0,20 ­ 4,00 mm², 24 ­ 10 AWG

2 core with the same cross section, flexible with
crimp connectors, no plastic sleeve

0,20 ­ 2,50 mm², 24 ­ 14 AWG

2 core with the same cross section, flexible without
crimp connectors or with TWIN crimp connectors

0,20 ­ 2,50 mm², 24 ­ 14 AWG

Torque setting with screw terminals

0,50 Nm

Connection type

Screw terminal

Mounting type

Fixed