PZE X4

Operating Manual PZE X4
1003199­EN­08

7

Installation

}

The unit should be installed in a control cabinet with a protection type of at least IP54.

}

Use the notch on the rear of the unit to attach it to a DIN rail.

}

Ensure the unit is mounted securely on a vertical DIN rail (35 mm) by using a fixing ele­
ment (e.g. retaining bracket or an end angle).

}

If more than 2 units are installed next to each other in the control cabinet, leave a dis­
tance of at least 6 mm between the units.

Wiring

Please note:

}

Information given in the "

Technical details [

 9]

" must be followed.

}

The outputs 13­14, 23­24, 33­34 and 43­44 are safety contacts.

}

To prevent contact welding, a fuse should be connected before the output contacts (see
Technical details).

}

Calculation of the max. cable runs l

max 

in the input circuit:

R

lmax

R

l

/ km

I

max

=

R

lmax

 = max. overall cable resistance (see Technical details)

R

l

 / km = cable resistance/km

}

Use copper wire that can withstand 60/75 °C.

}

Sufficient fuse protection must be provided on all output contacts with capacitive and in­
ductive loads.

}

Do not switch low currents using contacts that have been used previously with high cur­
rents.