Chapter 5: Diagnostics and Troubleshooting

59

If m odule status LED
is:

Indicated
condition

Corrective action:

On

Proper Operation

No action required

Of f

Module Fault

Cycle power. If
condition persists,
replace the module.
Call your local
distributor or
Spectrum Controls
for assistance.

Channel Diagnostics

When an input channel is enabled, the module performs a diagnostic check
to see that the channel has been properly configured. In addition, the
channel is tested on every scan for configuration errors, over-range and
under-range, and open-circuit conditions.

Invalid Channel Configuration Detection

Whenever a channel configuration word is improperly defined, the module
reports an error. See table 5.3 for a description of module errors.

Over- or Under-Range Detection

Whenever the data received at the channel word is out of the defined
operating range, an over-range or under-range error is indicated in input
data word 9. Possible causes of an out-of-range condition include:

The temperature is too hot or too cold for the type of thermocouple or

RTD being used.

The wrong thermocouple or RTD is being used for the input type

selected, or for the configuration that was programmed.

The input device is faulty.

The signal input from the input device is beyond the scaling range.