Spectrum Controls 1769sc-IF8u User Manual
Page 120
![background image](/manuals/742127/120/background.png)
110
Compact IO
™
Universal Input Module
the module type in the Controller Organizer. The Description field is
optional and may be used to provide more details concerning this I/O
module in your application.
The slot number must be selected next, although it will begin with the first
available slot number, 1, and increments automatically for each subsequent
Generic Profile you configure. For this example, the 1769sc-IF8U
Universal module is located in slot 1.
The Comm Format, Assembly Instance and Size values are listed in the
following table for the 1769sc-IF8U Universal module:
1769 I/O
Module
Com m Form at
Parameter
Assembly
Instance
Size
(16-bit)
IF8U
Input Data - INT
Input
Output
Config
101
104
102
11
0
18
Enter the Assembly Instance numbers and their associated sizes for the
1769sc-IF8U module into the Generic Profile. When complete, the
Generic Profile for a 1769sc-IF8U module should look like the following:
At this point you may click “Finish” to complete the configuration of your
I/O module.
Configure each I/O module in this manner. The CompactLogix5320
controller supports a maximum of 8 I/O modules. The valid slot numbers