beautypg.com

6compact io, Universal input module – Spectrum Controls 1769sc-IF8u User Manual

Page 16

background image

6

Compact IO

Universal Input module

Thermocouple and RTD measurements are linearized using the
specifications listed in the table below.

Input Type

Specification

100? Pt 385

IEC-751, 1983

200Ω Pt 385

IEC-751, 1983

500Ω Pt 385

IEC-751, 1983

1000Ω Pt 385

IEC-751, 1983

100Ω Pt 3916

JIS C 1604, 1989

200Ω Pt 3916

IEC-751, 1983

500Ω Pt 3916

IEC-751, 1983

1000Ω Pt 3916

IEC-751, 1983

10Ω Cu 426

SAMA RC21-4-1966

120Ω Ni 618

DIN 43760 Sept. 1987

120Ω Ni 672

MINCO Application Aid #18, Date 5/90

604Ω Ni Fe 518

MINCO Application Aid #18, Date 5/90

J

NIST ITS 90

K

NIST ITS 90

T

NIST ITS 90

E

NIST ITS 90

R

NIST ITS 90

S

NIST ITS 90

B

NIST ITS 90

N

NIST ITS 90

C

From the Annual Book of Standards, American Society for Testing Materials

Thermocouple measurements utilize a single cold junction compensation
sensor placed in the center of the terminal block. Thermocouple support
includes types J, K, T, E, R, S, B, N, C with a range to 100 mV. In
thermocouple mode the 1769sc-IF8u will measure thermocouple and CJC
sensor voltages and convert the results to a linearized temperature
reading. RTD support includes types Pt 385, Pt 3916, Ni 618, Ni 672, and
Cu 426. In RTD and resistance modes the module will inject a constant
current through the RTD or resistor, measure the voltage across the
resistance, and convert to a linearized temperature or resistance reading.
RTD and resistance input types support 2, 3, or 4-wire resistance
measurements.

When configured for current or voltage type inputs, the module converts
the analog values directly into digital counts.