6compact io, Universal input module – Spectrum Controls 1769sc-IF8u User Manual
Page 16
6
Compact IO
™
Universal Input module
Thermocouple and RTD measurements are linearized using the
specifications listed in the table below.
Input Type
Specification
100? Pt 385
IEC-751, 1983
200Ω Pt 385
IEC-751, 1983
500Ω Pt 385
IEC-751, 1983
1000Ω Pt 385
IEC-751, 1983
100Ω Pt 3916
JIS C 1604, 1989
200Ω Pt 3916
IEC-751, 1983
500Ω Pt 3916
IEC-751, 1983
1000Ω Pt 3916
IEC-751, 1983
10Ω Cu 426
SAMA RC21-4-1966
120Ω Ni 618
DIN 43760 Sept. 1987
120Ω Ni 672
MINCO Application Aid #18, Date 5/90
604Ω Ni Fe 518
MINCO Application Aid #18, Date 5/90
J
NIST ITS 90
K
NIST ITS 90
T
NIST ITS 90
E
NIST ITS 90
R
NIST ITS 90
S
NIST ITS 90
B
NIST ITS 90
N
NIST ITS 90
C
From the Annual Book of Standards, American Society for Testing Materials
Thermocouple measurements utilize a single cold junction compensation
sensor placed in the center of the terminal block. Thermocouple support
includes types J, K, T, E, R, S, B, N, C with a range to 100 mV. In
thermocouple mode the 1769sc-IF8u will measure thermocouple and CJC
sensor voltages and convert the results to a linearized temperature
reading. RTD support includes types Pt 385, Pt 3916, Ni 618, Ni 672, and
Cu 426. In RTD and resistance modes the module will inject a constant
current through the RTD or resistor, measure the voltage across the
resistance, and convert to a linearized temperature or resistance reading.
RTD and resistance input types support 2, 3, or 4-wire resistance
measurements.
When configured for current or voltage type inputs, the module converts
the analog values directly into digital counts.