Chapter 4: Module Data, Status, and Configuration

43

Table 4.2 Channel Data Word Format

? Celsius

? Fahrenheit

? Celsius

? Fahrenheit

J

-210 to 1200

-346 to 2192

-2100 to 12000

-3460 to 21920

0 to 16383

-32767 to 32767

0 to +10000

K

-270 to 1370

-454 to 2498

-2700 to 13700

-4540 to 24980

0 to 16383

-32767 to 32767

0 to +10000

T

-270 to 400

-454 to 752

-2700 to 4000

-4540 to 7520

0 to 16383

-32767 to 32767

0 to +10000

E

-270 to 1000

-454 to 1832

-2700 to 10000

-4540 to 18320

0 to 16383

-32767 to 32767

0 to +10000

R

0 to 1768

32 to 3214

0 to 17680

320 to 32140

0 to 16383

-32767 to 32767

0 to +10000

S

0 to 1768

32 to 3214

0 to 17680

320 to 32140

0 to 16383

-32767 to 32767

0 to +10000

B

300 to 1820

572 to 3308

3000 to 18200

5720 to 32767

1

0 to 16383

-32767 to 32767

0 to +10000

N

-210 to 1300

-346 to 2372

-2100 to 13000

-3460 to 23720

0 to 16383

-32767 to 32767

0 to +10000

C

0 to 2315

32 to 4199

0 to 23150

320 to 32767

1

0 to 16383

-32767 to 32767

0 to +10000

+/- 50 mV

-500 to 500

2

-500 to 500

2

-5000 to 5000

2

-5000 to 5000

2

0 to 16383

-32767 to 32767

0 to +10000

+/- 100 mV

-1000 to 1000

2

-1000 to 1000

2

-10000 to 10000

2

-10000 to 10000

2

0 to 16383

-32767 to 32767

0 to +10000

0 – 5 V

0 to 500

2

0 to 500

2

0 to 5000

2

0 to 5000

2

0 to 16383

-32767 to 32767

0 to +10000

1 – 5 V

100 to 500

2

100 to 500

2

1000 to 5000

2

1000 to 5000

2

0 to 16383

-32767 to 32767

0 to +10000

0 – 10 V

0 to 1000

2

0 to 1000

2

0 to 10000

2

0 to 10000

2

0 to 16383

-32767 to 32767

0 to +10000

+/- 10 V

-1000 to 1000

2

-1000 to 1000

2

-10000 to 10000

2

-10000 to 10000

2

0 to 16383

-32767 to 32767

0 to +10000

0 – 20 mA

0 to 2000

2

0 to 2000

2

0 to 20000

2

0 to 20000

2

0 to 16383

-32767 to 32767

0 to +10000

4 – 20 mA

400 to 2000

2

400 to 2000

2

4000 to 20000

2

4000 to 20000

2

0 to 16383

-32767 to 32767

0 to +10000

0 – 150 Ω

0 to 150

0 to 150

0 to 1500

0 to 1500

0 to 16383

-32767 to 32767

0 to +10000

0 – 1000 Ω

0 to 1000

0 to 1000

0 to 10000

0 to 10000

0 to 16383

-32767 to 32767

0 to +10000

0 – 3000 Ω

0 to 3000

0 to 3000

0 to 30000

0 to 30000

0 to 16383

-32767 to 32767

0 to +10000

Platinum 385

-200 to 850

-328 to 1562

-2000 to 8500

-3280 to 15620

0 to 16383

-32767 to 32767

0 to +10000

Platinum 3916

-200 to 630

-328 to 1166

-2000 to 6300

-3280 to 11660

0 to 16383

-32767 to 32767

0 to +10000

Copper 426

-100 to 260

-148 to 500

-1000 to 2600

-1480 to 5000

0 to 16383

-32767 to 32767

0 to +10000

Nickel 618

-100 to 260

-148 to 500

-1000 to 2600

-1480 to 5000

0 to 16383

-32767 to 32767

0 to +10000

Nickel 672

-80 to 260

-112 to 500

-800 to 2600

-1120 to 5000

0 to 16383

-32767 to 32767

0 to +10000

Nickel-Iron 518

-100 to 200

-148 to 392

-1000 to 2000

-1480 to 3920

0 to 16383

-32767 to 32767

0 to +10000

2

When voltage or current modes are selected, the temperature setting is ignored. Analog input data is the same for either °C or °F selection.

Percent

Range

Data Format

Input Type

Scaled For PID Proportional Counts

1

Type B and C thermocouples, Nickel 672, Nickel 618, Nickel-Iron 518, and Copper 426 cannot be represented in engineering units x 1 (°F) above

3276.7°F (or below -3276.7°F for Nickel-Iron 518). Softw are treats it as an over range error (or under range error for below -3276.7°F for Nickel-Iron
518).

Engineering Units x 10

Engineering Units x 1

NOTE The engineering units data formats represent real engineering
temperature units provided by the module to the controller. The raw/
proportional counts, scaled-for-PID and percent of full-scale data formats
may yield the highest effective resolutions, but may also require that you
convert channel data to real engineering units in your control program.

Raw/Proportional Data

The value presented to the controller is proportional to the selected input
and scaled into the maximum data range allowed by the bit resolution of
the A/D converter and filter selected. The raw/proportional data format
also provides the best resolution of all the data formats.

If you select the raw/proportional data format for a channel, the data word
will be a number between -32767 and +32767. For example, if a type J
thermocouple is selected, the lowest temperature of -210°C corresponds
to -32767 counts. The highest temperature of 1200°C corresponds to