Spectrum Controls 1769sc-IF8u User Manual
Page 116
106
Compact IO
™
Universal Input Module
!
When using the read IO configuration feature in RSLogix, you
need to manualy enter 18 into the “extra data length” field.
To configure the module select the Generic Extra Data Configuration
tab. Enter the decimal equivalent of each configuration word. There are
a total of 18 words that need to be configured altogether. The module
default settings are used if all the configuration words are left at zero..
NOTE For a complete description of each of these parameters and the
choices available for each of them, refer to chapter 4.
NOTE: Words 10 through 17 are reserved and must contain zero.
See also other documents in the category Spectrum Controls Measuring instruments:
- 1756sc-CTR8 (74 pages)
- 1756sc-HART Modules (170 pages)
- 1756sc-IF8u (118 pages)
- 1769sc-HART Modules (186 pages)
- 1769sc-HART Modules (176 pages)
- 1769sc-IT6I (82 pages)
- 1769sc-IR6I (74 pages)
- 2080sc-IF4u (12 pages)
- 2080sc-OW2IHC (10 pages)
- 2080sc-NTC (30 pages)
- 2080sc-BAC (56 pages)
- 1762sc-IF8U (12 pages)
- 1762sc-IF8U (38 pages)
- 1762sc-IF4OF4 (12 pages)
- 1762sc-IF4OF4 (42 pages)
- 1762sc-OF8 (12 pages)
- 1762sc-OF8 (42 pages)
- 1734sc-IE4CH (84 pages)
- 1734sc-IF4U (50 pages)
- 1734sc-OE2CIH (74 pages)
- 1794sc-IF8IU (3 pages)
- 1794sc-IF8IU (56 pages)
- 1794sc-IRT8I (3 pages)
- 1794sc-IRT8I (54 pages)
- 1746sc-CTR4 (66 pages)
- 1746sc-INI4vi (58 pages)
- 1746sc-INO4vi (48 pages)
- 1746sc-NI8u (130 pages)
- 1746sc-IA8i (27 pages)
- 1771sc-IFE32 (50 pages)
- 1771sc-IMI16 (8 pages)
- 140 MPM 204 00sc (66 pages)
- 140 EHC 208 00sc (81 pages)
- 140 AUI 040 00sc (52 pages)
- 140 ACI 051 00sc (57 pages)
- 140 ACI 052 00sc (62 pages)