72

ControlLogix

Universal Analog Input Module

RTD Conversion

JIS C 1602-1997 for Pt 385

JIS C 1604-1989 for Pt 3916

SAMA RC21-4-1966 for the 10

Ω Cu 426 RTD

DIN 43760 Sept. 1987 for the 120

Ω Ni 618 RTD

MINCO Application Aid #18 May 1990 for the 120

Ω Ni 672 RTD

Thermocouple

NIST ITS-90 standard

Linearization

RTD Current Source

252μA or 1.008mA, one for each RTD channel

Cold Junction

Compensation

2 Onboard CJC Sensor Required

Input Impedence

Greater than 1M

Ω > Ohm Voltage / Thermocouple / RTD

< 250

Ω current

Temperature Scale

°C or °F

(Selectable)

Open Circuit Detection

via Underrange

Does not apply to ±10V range

Time to Detect

< 5 Seconds

Open Circuit

Input Step Response

0 to 95% in 190 msec (50/60 Hz)

Display Resolution

IEEE Floting Point

Overall Module Accuracy

See Module Accuracy Tables below

@ 25°C (77°F)

Overall Module Accuracy

See Module Accuracy Tables below

(0°C to 60°C, 32°F to 140°F)

Overall Module Drift

See Module Accuracy Tables below

Module Update Time

Dependent upon enabled channels (see Update Time, Chap 3)

Channel Turn-Off Time

Up to one module update time

Overall Accuracy

The accuracy of the module is determined by many aspects of the
hardware and software functionality of the module. The following
attempts to explain what the user can expect in terms of accuracy based
on the thermocouple, RTD, resistance, and millivolt, volt, and milliamp
inputs for the IF8u module.

The accuracies specified as follows include errors due to the cold junction
compensation for thermocouples, current source errors for RTDs, and
hardware and software errors associated with the system, which depends
upon input path. RTD accuracies do not include errors due to lead