beautypg.com

Spectrum Controls 1756sc-IF8u User Manual

Page 82

background image

70

ControlLogix

Universal Analog Input Module

Physical

Specifications

LED Indicators

1 red/green status indicators, 1 red calibration status

Recommended Cable:

for thermocouple inputs...

Shielded twisted pair thermocouple extension wire

for mV, V or mA inputs

Belden 8761 or equivalent

for RTD inputs

shielded Belden #9501, #9533, #83503

Maximum Wire Size

One 2.1 mm

2

(16 AWG) wire or two 0.25 mm

2

(22 AWG) wires per

terminal

Refer to the thermocouple manufacturer for the correct extension wire.

Refer to the RTD manufacturer and Chapter 1 of this user’s manual.

ATEX Special Conditions for Safe Use

Provision shall be made to prevent the rated voltage being exceeded by the transient disturbances of more than

140% of the peak rated voltage.

The system shall be mounted in an ATEX certified enclosure with a minimum ingress protection rating of at

least IP54 as defined in IEC60529 or EN60529 and used in an environment of not more than pollution degree 2.

The enclosure shall be accessible with the use of a tool.

Environmental

Specifications

Operating Temperature

0°C to 60°C (32°F to 140°F)

Storage Temperature

-40°C to 85°C (-40°F to 185°F)

Relative Humidity

5% to 95% (without condensation)

Certification

UL & CUL approved

UL 508

2006/95/EC Low Voltage Directive

2004/108/EC Electromagnetic Compatibility

94/9/EC ATEX

CE compliance to EN 61010-1, EN 61131-2, EN61000-6-2

EN61000-6-4

Hazardous Environment

Class I Division 2 T5 Hazardous Environment

Classification

Groups A, B, C, D

Input Specifications

Thermocouple Type J

-210°C to 1200°C

(-346°F to 2192°F)

Thermocouple Type K

-270°C to 1372°C

(-454°F to 2502°F)

Thermocouple Type T

-270°C to 400°C

(-454°F to 752°F)

Thermocouple Type E

-270°C to 1000°C

(-454°F to 1832°F)

Type of Input (Selectable)

Thermocouple Type R

0°C to 1768°C

(32°F to 3214°F)

Thermocouple Type S

0°C to 1768°C

(32°F to 3214°F)