beautypg.com

Spectrum Controls 1756sc-IF8u User Manual

Page 58

background image

46

ControlLogix

Universal Analog Input Module

.LAlarmLimit

REAL

A low alarm will activate if the value of the scaled input is at or below this

value. It will clear, if not latched, if it is above this level plus the

.AlarmDeadband amount.

.HAlarmLimit

REAL

A high alarm will activate if the value of the scaled input is at or above this

value. It will clear, if not latched, if it is below this level plus the

.AlarmDeadband amount.

.LLAlarmLimit

REAL

A low-low alarm will activate if the value of the scaled input is at or below

this value. It will clear, if not latched, if it is above this level plus the

.AlarmDeadband amount.

.HHAlarmLimit

REAL

A high-high alarm will activate if the value of the scaled input is at or

above this value. It will clear, if not latched, if it is below this level plus the

.AlarmDeadband amount.

.AlarmDeadband

REAL

A value used for determining when an alarm condition goes away. See

it’s use in the above alarm tags.
Input Signal Scaling:

With scaling, you change a quantity from one notation to another. When

you scale the module, you must choose two points along the module’s

operating range and apply low and high values to those points. For

example,you can cause a 4mA input to display 0% and a 20mA input to

display 100%. Scaling causes the module to return data to the controller

so that 4mA returns a value of 0% in engineering units and 20mA returns

a value of 100% in engineering units.

The module may operate with values beyond the 4mA to 20mA range. If

an input signal beyond the low and high signals is present at the module

(e.g.3mA), that data will be represented in terms of the engineering units

set during scaling. For example...

Configuration:

.RangeType = 6 (0-20mA)

.LowSignal = 4 (4mA)

.HighSignal = 20 (20mA)

.LowEngineering = 0 (0%)

.HighEngineering = 100 (100%)

Note: If the signal and engineering range are left at zero, the default

range is utilized. Refer to pages 2 and 3 for valid signal and engineering

ranges.