Chapter 2: Installing And Wiring Your Module

19

RTD Type

Current Source V/

°

C

100

Ω

Pt 385

1.008mA

357µV/

°

C

200

Ω

Pt 385

1.008mA

714µV/

°

C

500

Ω

Pt 385

252

µA

447µV/

°

C

1000

Ω

Pt 385

252

µA

893µV/

°

C

100

Ω

Pt 3916

1.008mA

377µV/

°

C

200

Ω

Pt 3916

1.008mA

754µV/

°

C

500

Ω

Pt 3916

252

µA

472µV/

°

C

1000

Ω

Pt 3916

252

µA

941µV/

°

C

120

Ω

Ni 618

1.008mA

694µV/

°

C

200

Ω

Ni 618

1.008mA

1389µV/

°

C

500

Ω

Ni 618

252

µA

867µV/

°

C

1000

Ω

Ni 618

252

µA

1733µV/

°

C

10

Ω

Cu 426

252

µA

9.7µV/

°

C

120

Ω

Ni 672

1.008mA

929µV/

°

C

The accuracies specified for the IF8u RTDs do not include errors due to
lead resistance imbalances.

Important: To ensure temperature or resistance value accuracy, the
resistance difference of the cable lead wires must be equal to or less than
0.01 ohms.

Important: Keep total lead resistance as small as possible and less than
25 ohms.

There are several ways to insure that the lead values match as closely as
possible. They are as follows:

* Use quality cable that has a small tolerance impedance rating.

* Use a heavy gauge lead wire which has less resistance per foot.