Spectrum Controls 1756sc-IF8u User Manual
Page 31
Chapter 2: Installing And Wiring Your Module
19
RTD Type
Current Source V/
°
C
100
Ω
Pt 385
1.008mA
357µV/
°
C
200
Ω
Pt 385
1.008mA
714µV/
°
C
500
Ω
Pt 385
252
µA
447µV/
°
C
1000
Ω
Pt 385
252
µA
893µV/
°
C
100
Ω
Pt 3916
1.008mA
377µV/
°
C
200
Ω
Pt 3916
1.008mA
754µV/
°
C
500
Ω
Pt 3916
252
µA
472µV/
°
C
1000
Ω
Pt 3916
252
µA
941µV/
°
C
120
Ω
Ni 618
1.008mA
694µV/
°
C
200
Ω
Ni 618
1.008mA
1389µV/
°
C
500
Ω
Ni 618
252
µA
867µV/
°
C
1000
Ω
Ni 618
252
µA
1733µV/
°
C
10
Ω
Cu 426
252
µA
9.7µV/
°
C
120
Ω
Ni 672
1.008mA
929µV/
°
C
The accuracies specified for the IF8u RTDs do not include errors due to
lead resistance imbalances.
Important: To ensure temperature or resistance value accuracy, the
resistance difference of the cable lead wires must be equal to or less than
0.01 ohms.
Important: Keep total lead resistance as small as possible and less than
25 ohms.
There are several ways to insure that the lead values match as closely as
possible. They are as follows:
* Use quality cable that has a small tolerance impedance rating.
* Use a heavy gauge lead wire which has less resistance per foot.