Spectrum Controls 1756sc-IF8u User Manual
Page 52
![background image](/manuals/742124/52/background.png)
40
ControlLogix
™
Universal Analog Input Module
Input Type:
Each input type has a specific settling time. Select each channel input
type and add the time value.
Time (ms)
Type
Tag: .RangeType
0
All voltage, current, and thermocouple types
3
100_Pt_385
8
3
100_Pt_392
12
3
120_Ni_618
16
3
120_Ni_672
20
3
10_Cu_426
21
3
604_NiFe_518
22
3
0_250_Ohm
23
3
0_500_Ohm
24
4
200_Pt_385
9
4
500_Pt_385
10
4
200_Pt_392
13
4
500_Pt_392
14
4
200_Ni_618
17
4
500_Ni_618
18
4
0_1000_Ohm
25
4
0_2000_Ohm
26
8
1000_Pt_385
11
8
1000_Pt_392
15
8
1000_Ni_618
19
8
0_3000_Ohm
27
8
0_4000_Ohm
28
Example 1:
4 channels with 200 Ohm PT 385 RTD (Input Type 9) at 100Hz filter =
18ms + 4ms = 22ms * 4 channels = 88ms
2 channels of voltage at 1khz = 2 * 6ms = 12ms
2 thermocouples at 250Hz = 2 * 10ms = 20ms
Total = 5ms (overhead) + 26ms (CJC) + 88ms + 12ms + 20ms = 151ms
(Actual measured = 158ms)
Example 2:
8 channels, 0-4000 ohm (type 28) at 250Hz = 10ms + 8ms = 18ms * 8 =
144ms + 5ms = 149ms. (Actual measured = 117ms)
Note: This is approximation only. The time changes because the software
does not need to spend time setting up the ADC for another filter
frequency if it is the same as the previous channel. The same applys for
the the gain settings, etc. Example 2 illustrates there is a significant
savings because the filter frequency and input type are the same.
Note: If the autocalibration is enabled the module sampling time will
increase by as much as 500ms when autocalibration is being performed.